I have an UPS with two 12v 7ah lead batteries. If I want to change the batteries I would typically go with lead batteries but here’s my question, can I use some portable mobile batteries to use it?
Because I have a 20000mah inui battery that is rated for 12v at 1.5A is this a good practice to buy several of these (since they are about 20 bucks) disassemble them and use them as ups batteries?
You need a balancing BMS anyway and the UPS will not be able to charge it to what it thinks is 100% (about 15 V at trickle current) unless you trick it with a resistor (which wastes power of course).
Yeah you need a UPS that’s OK with the BMS charge FETs opening when the battery is full.
When there is no trickle current the UPS will beep because it will detect battery removal.
Some are ok with it, on a thread I saw on reddit awhile ago about LiFePo4, people had reported a few models that worked fine with the upgrade.